General specification

Designation Data
Power supply 12, 24, 48, 110, 220 VDC
12, 24, 115, 230 VAC, 50-60 Hz
Current consumption Max. 150 mA, 50 mA normal at 24 VAC
Power consumption Max. 5 W
Environment -10 deg.C to +40 deg.C, Rh. max. 75%
Protection IP 51 or IP 54 as specified in IEC 529
Insulation Class II, double insulation
External wire resistance Max. 10 kohm per channel
Electrical safety SS-EN 61010-1:1993
EMC protection Emission: EN 61000-6-3:2001
Immunity: EN 61000-6-2:2001
Output relay contact effect Max. 250 VAC, 5 Amp, max 1250 VA
Inputs, alt. a Supply from the alarm unit
Inputs, alt. b External supply 12 - 230 VAC/DC (opto input)
Time delay, preprogrammed 2 msec to 10 minutes
Time delay, adjustable 0,2 to 35 seconds
Priorities, alt. a Only A alarm
Priorities, alt. b A or B alarms, programmable for each channel
Failure modes, alt. a Closing failure contacts, programmable for each channel
Failure modes, alt. b Breaking failure contacts, programmable for each channel
Failure modes, alt. c Closing or breaking failure contacts, programmable for each channel
Summary relay Closing or breaking
Test, alt. 1 Total check incl. test of relay
Test, alt. 2 Total check excl. test of relay
Reset, alt. a Only manually
Reset, alt. b Manually or automatically, programmable for each channel